IAQ020

logo ruskin 60px

IAQ020

The IAQ020X Control Package comes standard with the IAQ50X Air Measuring Station. Combined, the IAQ020X and IAQ50X offer a complete turnkey solution for measuring and controlling the minimum outside air to ASHRAE Standard 62.

The complete assembly (including IAQ50X air measurement damper, 24 VAC MS75XXIAQ actuator and IAQ020X control panel) is factory commissioned and calibrated to insure overall compatibility. The actuator is calibrated at multiple points along the 90° cycle. The control module utilizes the actuator feedback to confirm damper position and calculate the CFM (l/s) output based on both pressure and damper blade position. CFM (l/s) setpoint control with a 0-10 VDC input from the BAS. Provides a 0-0 VDC output that is proportional to the CFM (l/s) and modulates the damper position to maintain setpoint CFM (l/s) value.

CONTROLLER SPECIFICATIONS

  • CONTROLLER ENCLOSURE Plenum-rated enclosure meets UL94-5V
  • ELECTRICAL ENCLOSURE 18" x 18" x 6" (457 x 457 x 152) NEMA 1 (painted finish)
  • SUPPLY VOLTAGE 120 Vac, 50/60 Hz, 85VA Max Controller: 18VA Transducer: 10VA (1) Actuator: 16VA driving, 5VA Holding
  • INPUT SIGNAL 0-10 VDC from BAS or other source OUTPUT SIGNAL 0-10 VDC proportional to CFM (l/s)
  • PRESSURE TRANSDUCER AMS800.
  • AGENCY LISTINGS Controller: - UL916 & cUL916 (E14480) Class 2 device; FCC Part 15 Subpart J, Class A Transducer: CE, Conforms to EMC standards EN50082-1/EN55014/EN60730-1 Transformer: None
  • OPERATING RANGE Operating Temperature: 0° F to +150° F (-17.8° C to +65.6° C) Relative Humidity: 10% to 90% non-condensing
  • PROGRAM MEMORY Program logic & calibration in nonvolatile EPROM
  • VELOCITY PRESSURE INPUT 0.0 to 1.0 inches water column (0.0 to 249 Pa) (operating) 0.01 to 1.0 inches water column (2.49 to 249 Pa) (control) ±5% accuracy @ 1 inch water column (249 Pa) and 77°F (25°C).

Related items

  • MDRS25 MDRS25

    The MDRS25 is a ruggedly built round manual balancing damper with factory mounted, locking hand quadrant designed especially for manual balancing applications within round spiral ductwork.

  • MD35 MD35
    The MD35 Manual Balancing Damper has a 5" frame.
  • MD25 MD25
    The MD25 Manual Balancing Damper has a 3" frame.
  • MD15 MD15
    The MD15 is a ruggedly built, inexpensive damper with stand-off bracket for the hand quadrant both factory furnished. It is designed for manual balancing applications with rectangular ductwork. 
  • ELM6DW ELM6DW
    The ELM90 Adjustable Louver is 6" deep and has a 37 1/2 degree blade angle.
More in this category: « EFAMS IAQ350XL »

Air Delivery

  • TDL Series
    TDL Series AirConcepts is excited to introduce the new Model TDL-Turret Drum Louver, a Drum Louver with a turret swivel design to…
    in Industrial Diffusers

Life Safety

Air Measuring

More Control

  • Room Humidity/Temp Sensor
    Room Humidity/Temp Sensor The HU-225 is an extremely fast, stable and accurate humidity/temperature transducer designed for harsh environments. The polymer humidity capacitance sensor…
    in Humidity

Proudly Representing

logo ruskin 60px logo nailor 60pxh ACME Logo Air Concepts FlexmasterLogo

InetSupervisor thermal header Engineered Comfort Mamac Logo